Skip to main content
Electronic Theatre Controls Inc

Status Messaging or Telegrams with Echoflex Controllers

Question

What is status messaging or status telegram for Echoflex Controllers and Interface and how can I utilize it?

Is there a way to monitor the current status of an Echoflex Controller or Interface?

Description

Normally Echoflex communication is a one-way street, with control devices sending signals to output controllers and interfaces that count as outputs. Status messaging/telegram is a special case that allows an output controller/interface to report its current status, which serves two main purposes:

  • To monitor and interpret the status via Garibaldi or DolphinView to assist with troubleshooting equipment.
  • To provide feedback to interfaces/gateways that use the status to trigger other commands.

This feature is disabled by default and can be enabled/disabled via the physical buttons on the unit or the Garibaldi commissioning program.

Manual Steps at the Device

To enable:

  • Press and hold the [LEARN] button.
  • Tap the [CLEAR] button twice.
  • Release the [LEARN] button. The 'learn' LED should blink twice to confirm the double tap.

To disable:

  • Press and hold the [LEARN] button.
  • Tap the [CLEAR] button once.
  • Release the [LEARN] button. The 'learn' LED should blink once to confirm the single tap.

Video Walkthrough

 

 