Skip to main content

 

 

 

 

Electronic Theatre Controls Inc

Connecting 0-10v control to RAYN Inventronics Drivers

The INVENTRONICS drivers have 3 wires in the 0-10v Input.

Dim + (PUR) 0-10v control

Dim - (GRY) 0-10v control

VAux (BLK/WHT) Used to power the INVENTRONICS DS- CNV-DMXR DMX to 0-10 Controller.

When ganging 0-10v control together Do not connect VAux together, you will find one or more drivers stop outputting. If you find VAux is connected across multiple drivers, remove the wire ganging them together.

When using with Pathway's PWINF DMX to Analog Interface, use in Source mode.

  • Was this article helpful?