Issue
I have a Contact Input option card for my Echo Relay Panel Mains Feed (ERP), Echo Relay Panel Feedthrough (ERP-FT), SensorIQ, or EchoDIN product, along with a momentary button, and I'd like to set it up with a toggle action, so one push of the button will turn a preset on, and a second push of the button turns the preset off. Is this possible?
Explanation of Issue
Unfortunately this is not actually possible using the Contact Input option card. While a contact can be configured for momentary operation, the closed/open actions on the Echo Power Control Processor can only be configured for discrete actions, like Preset Activate and Off. With a momentary button this results in activating a preset when pushing the button, but playing Off (or another defined action) as soon as the button is released. This is not ideal, so several alternate solutions are provided below.