Can the ELTS2 detect a Brown Out or Loss of Voltage?
Explanation
The ELTS2 can detect a brown out or a dip in voltage, although it will only detect and switch over on set values that cannot be changed.
Refer to the table below for information on which voltages will trigger a transfer.
Event | 120 VAC Models | 240 VAC Models | 277 VAC Models |
---|---|---|---|
Emergency Phase A Pickup Voltage | 100 VAC | 200 VAC | 240 VAC |
Normal Phase A Dropout Voltage | 80 VAC | 160 VAC | 185 VAC |
Normal Phase A Pickup Voltage | 100 VAC | 200 VAC | 240 VAC |
Normal Phase B Dropout Voltage | 80 VAC | 160 VAC | 80 VAC |
Normal Phase B Pickup Voltage | 81 VAC | 162 VAC | 81 VAC |
Normal Phase C Dropout Voltage | 80 VAC | 160 VAC | 80 VAC |
Normal Phase C Pickup Voltage | 81 VAC | 162 VAC | 81 VAC |