ELTS 2 Remote Station Wiring

Explanation

To wire in an Emergency Lighting Transfer Switch 2 (ELTS 2) station, you will need five 16 AWG wires from the ELTS 2 to the Remote Station.

On the ELTS 2 control card, the wiring will terminate on terminal J2 in the following pinout order:

elts2RemoteStation.jpg

 

 

  1. +24V Common
  2. Normal Switch
  3. Emergency Switch
  4. Normal Mode LED
  5. Emergency Mode LED

 

 

 

When landing on the station, you will want to match this pinout order starting with Pin 1 on Terminal TB1.

On the station itself, Pin 6 is not used.

 

More information can be found in the ELTS 2 Installation Manual on Page 21 and Page 22.