ELTS 2 Remote Station Wiring
Explanation
To wire in an Emergency Lighting Transfer Switch 2 (ELTS 2) station, you will need five 16 AWG wires from the ELTS 2 to the Remote Station.
On the ELTS 2 control card, the wiring will terminate on terminal J2 in the following pinout order:
- +24V Common
- Normal Switch
- Emergency Switch
- Normal Mode LED
- Emergency Mode LED
When landing on the station, you will want to match this pinout order starting with Pin 1 on Terminal TB1.
On the station itself, Pin 6 is not used.