Problems with Strand SN110 node receiving DMX

From our testing, Strand SN110 DMX nodes seem to require more than a 6 millisecond idle time after the last stop bit.  In order for ETC consoles, DMX nodes, and gateways to communicate with an SN110 via DMX, you must set the ETC device's DMX Output Speed to "slow".  A deep clear or reset of an ETC device will default the DMX speed to Fast or Max", so the setting will need to be changed again.