How Do I Wire a Contact Closure to the Response Analog I/O Gateway?

Issue

I have an On/Off contact closure that I want to use with my Response Analog I/O Gateway as an input.

Explanation of Issue

The Response Analog I/O Gateway can accept any 10V input as a closure or measured value. If your contact is a "dry" contact and does not provide its own 10V, the Gateway's +10V can be used.

Solution

Dry Contact (no voltage provided by contact)

Analog Dry Contact.png

  1. Land one side of the contact to the desired input number.
  2. Land the other side of the contact to the Gateway's +10V

Wet Contact (10V provided by contact)

Analog Wet Contact.png

  1. Land one side of the contact to the desired input number.
  2. Land the other side of the contact to the COM next to the input