Dimmer Doubling DD (Multiplexing) sets Threshold to 50%
Problem:
When dimmers are set to a mode of DD (Dimmer Doubled), the Threshold becomes 50%. It can be changed back to normal, but happens every time.
Answer:
This is a bug in CEM software version 3.0. It is fixed in version 3.1.
Note: The CEM will need to come in for repair for the upgrade, all controllers will have to be updated to the same version of code. Upgrades are done on a limited basis due to chip availability.