L86 EM264 Loaners with Custom Tables
Issue
When installing a loaner EM264 unit, you may see a blinking error light.
If the "table" dip switches (1,2,3) are all in the up or enabled position, then the EM264 has a custom patch table, and the unit is unable to read this patch.
Fix/Solution
- Trade chips U21-U25 from the original unit to the loaner unit as these contain the software and configuration table.
- Ensure that the other dip switches and wheels match settings on the original EM264 exactly.