"Looking for Circuit" Error in Set Circuits on CEM3

Issue

When trying to Set Circuits from the test menu on a CEM3, I get an error that says "Looking for Circuit" and I'm unable to turn the light on.

Explanation of Issue

The circuit number you've entered does not exist in the rack configuration. This would be caused by someone having intentionally changed the circuit number in the configuration, or a module of a different density was changed and the configuration automatically skipped a circuit number. For example, if a D20 module is in the configuration at circuits 55 & 56, and you change the module type to D50AF, the circuit number will change to 56 and 55 will no longer exist.

Two Solutions

  1. On the CEM3 navigate to:

    Setup > Circuit Assignment > Edit Circuit Layout
    Scroll to the lug/module in question. Either notate the correct circuit number and use that instead, or change it to the number you prefer.
  2. Connect to the CEM3 using Net3 Concert and notate the correct circuit number and use that instead, or change it to the number you prefer and upload the changes to the CEM3.