CEM3 Airflow Error

Symptoms/Issue

CEM3 is reporting an Airflow Error

Explanation of Issue

CEM3s do not have a built-in airflow sensor and cannot inherently self-report. It requires a code generated by an AF card within a Sensor rack. In the event an airflow error is thrown, the CEM3 is not suspect. One or more modules or any AF cards could be at fault

Corrosion can cause this issue

Fix/Solution

  1. Power off the Sensor rack and reseat modules
  2. Power on the rack and check if the error returns
  3. If error persists, a technician or electrician may be needed to inspect the rack for corrosion

If needed, contact ETC Technical Support for further assistance