CEM "Config Mismatch" Error

Important-Icon.png

The information in this post is provided to assist in troubleshooting. Perform work at your own risk. ENSURE ANY POWER FROM DEVICES HAS BEEN DISCONNECTED BEFORE SERVICING ANY EQUIPMENT. If you do not feel comfortable performing the work, please contact us or your local service center. Be aware that ETC and its Affiliates are not responsible for any damage or injury caused by service of our products by anyone other than us or our authorized service providers, and such damage is excluded from the product’s warranty.

All CEMs on an ETCLink network contain the configuration for the entire system.  Each CEM controls only its own rack, which is defined by the CEM's ETCLink (Rack) address. 

Description of Issue

A "Configuration Mismatch" error indicates that one or more CEMs do not contain the same system configuration as the other CEMs.  This is typically a problem when a loaner or spare CEM is placed into the system.  This can also occur after a rack transfer to one CEM in a multirack system.

Fix

In this situation, the correct configuration from a known-good CEM can be downloaded into the CEM with the wrong configuration.  Note that multiple CEMs may show the error, which merely means that one CEM on the network is not like the others. 

Note-Icon.png To help determine which CEM has the wrong configuration, find the CEM which will not allow its ETCLink address to be changed to the highest number rack (e.g. 4-Rack system, one CEM will only allow an ETCLink address of 1 or 2--this is the problem CEM). If all CEM's will allow the highest-rack ETCLink address to be set, you must use other methods to find the rogue CEM, such as looking at Rack types, dimmer types, etc.

To download the configuration, go to the Setup-->Rack menu on the CEM with the incorrect configuration.  

  • In CEM 2.x, go to "Setup Rack Load Config From X", [Enter], "ETCLink Address", [Enter]. 
  • In CEM 3.x, go to "Setup Rack Transfer Local Rack Addr:X", [Enter], "Setup Rack Load Config From: X", [Enter]. 

You may need to hit reset on all CEMs which show the "Config Mismatch" error before the error will clear.